An industrial water cooling system is designed to reject heat generated from manufacturing processes, machinery (such as air compressors, injection molding machines, and furnace jackets), or HVAC systems.
These systems generally fall into three main categories: Open-Loop Cooling Towers, Closed-Circuit Fluid Coolers, and Industrial Water Chillers.
| System Type | Operating Principle | Typical Process Outlet Temp | Best For |
| Open-Loop Cooling Tower | Process water directly contacts airflow; cooling occurs via latent heat of evaporation. | $28circtext{C} text{ to } 32circtext{C}$ (depends on wet-bulb temp) | Large-scale heat rejection (steel mills, power plants, chemical processes). |
| Closed-Circuit Cooling Tower | Process fluid stays inside a sealed coil loop while spray water and air cool the exterior of the coil. | $28circtext{C} text{ to } 35circtext{C}$ | Applications requiring clean process loops (no scale/contamination inside equipment). |
| Industrial Water Chiller | Mechanical refrigeration cycle (compressor, evaporator, condenser) cools water actively. | $5circtext{C} text{ to } 20circtext{C}$ (or lower with glycol) | Precise temperature control, high heat density, or sub-ambient cooling needs. |
Cooling Capacity: Measured in Tons of Refrigeration (TR) ($1text{ TR} = 3.517text{ kW} = 12,000text{ Btu/hr}$) or kW/kcal/hr.
Flow Rates & Delta T ($Delta T$):
Standard design $Delta T$ (Supply vs. Return): $5circtext{C} text{ to } 10circtext{C}$ (e.g., $32circtext{C}$ inlet / $27circtext{C}$ outlet).
Standard flow requirement: 0.24 to 0.30 $text{m}3/text{h}$ per TR ($1 text{ to } 1.3 text{ GPM/TR}$) for cooling towers.
Operating Pressure: Designed for $4 text{ to } 6 text{ bar(g)}$ loop working pressure.
Heat Exchangers & Structure:
Cooling Tower Casing: Fiber-Reinforced Plastic (FRP), Stainless Steel 304/316, or Galvanized Steel.
Fill Media: PVC cross-fluted film fills for clean water; splash fills for dirty/high-debris process water.
Plate Heat Exchangers (PHE): Gasketed or Brazed AISI 316 Stainless Steel heat exchangers used to separate process loops from raw cooling tower water.
Pumping & Distribution Package:
Circulation Pumps: End-suction centrifugal or vertical multistage pumps in $N+1$ redundant configurations.
Variable Frequency Drives (VFDs): Applied to pumps and tower fans to optimize power usage based on ambient wet-bulb temperature fluctuations.
Water Treatment & Filtration Sub-System:
Side-stream Filtration: Sand filters or disc filters handling 5%10% of total flow rate to trap suspended solids.
Chemical Dosing Skids: Dosing of biocide, scale inhibitors, and corrosion inhibitors to manage Cycles of Concentration (CoC) and prevent Legionella growth.
Make-up Water Supply: Required for open towers to replace water lost to evaporation ($sim 1.8%$ per $10circtext{F} / 5.5circtext{C} Delta T$), drift, and blowdown.
Water Quality Limits:
pH Range: $6.8 text{ to } 8.2$
Total Dissolved Solids (TDS): $< 1,500 text{ to } 2,500text{ ppm}$
Chloride Content: $< 200text{ ppm}$ (for SS304) or $< 800text{ ppm}$ (for SS316)
Hardness ($text{CaCO}_3$): $< 200 - 300text{ ppm}$

Price:
Price 25000 INR / Piece
Minimum Order Quantity : 1 Piece
Type : Heat Pump
Power Source : Other, Electric
Color : Teal & Black
Voltage : 220440 V
Price 550000.0 INR / Piece
Minimum Order Quantity : 1 Unit
Type : OIL CHILLER
Power Source : Electrical
Color : ORANGE/IVORY
Voltage : 380420 Volt (v)
Price 325000 INR / Piece
Minimum Order Quantity : 1 Piece
Type : Scroll Chiller
Power Source : Electrical
Color : White/Blue